TRANSFORMER TEST
How to test transformer and types of electrical transformer testing.
There are many ways of testing transformer. Types of transformer test are including such as megger transformer test, winding resistance transformer test, ratio transformer test, no load loss transformer test, full load transformer test, impedance transformer test, continuity transformer, insulation resistance transformer test, polarity transformer test.
The above equation shows that the eddy current
loss depends on the flux density, frequency and thickness of the material and
inversely proportional to the resistivity of the material.
the total load current is measured by the meter connected across their high voltage winding
A number of tests are required to
physically determine the electrical characteristics of power and distribution
transformers. Many of those tests are indicated below:
In “REB” workshop has done 9 tests
for a transformer those are:
There are many Testing
Transformer
● Megger test (Insulation resistance test)
● Winding resistance test
● Ratio test
● No-load loss test
● Full load loss test
● Impedance test
● Continuity
test
● Insulation
resistance test
● Polarity test
Megger Test (Insulation Resistance
Test)
I use a Megger meter to measure the insulation resistance. Its
range is 0 to 1000+.Megger meter has two terminals. At the starting of Megger
testing, I connect two terminals to the body (short) to set Megger pointer at
“0” position. Then I connect body to HV side. 1000. Then I connect one terminal
to HT side another terminal to LT side. Megger shows 1000. If any fault occurs,
then in Megger meter not show 1000. 1000 means that insulation resistance
property is Ok of transformer. Then I record Megger readings on
Measure from high to low voltage
winding HL-G |
HT+GROUND |
LT+EARTH |
HT+LT |
Remark |
01 |
1000+ |
1000+ |
1000+ |
Ok |
Impedance Test
For impedance test I need max voltage in HV and the minimum
that voltage (HT) which can supply full load current in LT side. The 100 kVA
transformer is rated for 11 kV. So, 11000 V is the maximum voltage. By that
given bellow equation I can test impedance. So, the impedance is:
Full Load Loss Test
Full load
loss check is employed to work out copper loss in electrical device at full
load. Full load loss check is additionally called short check on electrical
device. The check is conducted on the high voltage (HV) facet of the electrical
device wherever the low voltage (LV) facet or the secondary is brief circuited.
For this check we want a watt meter, 3 section voltage offer, clamp meter and
wire for brief LT. After shorted the LT terminal, we tend to connect the HT 3
terminals with three section offer than the faucet changer position is in
three. when connecting HT terminal with three section offer, then we tend to
activate the three-phase voltage offer regulator to provide 3 section voltage
in HT terminal. the availability voltage needed to flow into rated current
through the electrical device. I applied three section voltage 399 V (red),
four hundred V (yellow), 393 V (blue) in HT terminal for one hundred kVA
electrical device. I actually have to live full load current in 3 terminals in
LT facet. AN engineer is measure full load current with clamp meter. For one
hundred kVA electrical device we tend to measured current ar 259 A, 260 A and
254 A in LT terminal. The wattmeter is connected with HT facet. The core losses
ar terribly tiny as a result of applied voltage is barely many percentages of
the nominal voltage and therefore may be neglected. Thus, the wattmeter reading
measures solely the complete load copper loss. For one hundred kVA electrical
device, full load loss shown in 310 W in watt meter. The watt meter issue is
two. So, I actually have to multiply the wattmeter reading with two. For one
hundred kVA electrical device full load loss is 310/2 = a hundred and fifty
five W. when measure full load loss, recorded in check result type.Table 5.2: Full Load Loss Test
SL |
Transformer
SI number |
kVA
rating |
Full
load loss Amp (Watt) |
1 |
2017-10-48770 |
100 |
150 |
2 |
2017-10-48550 |
100 |
155 |
3 |
2017-10-48796 |
100 |
152 |
4 |
2017-10-49163 |
100 |
148 |
|
|
|
|
The purpose of the short check is to work out
the copper loss occur on the total load.
The equivalent resistance, impedance, and
discharge electrical phenomenon ar best-known by the short check.
in brief circuit check or full Load check we'd
short the secondary winding of the electrical device.
The copper loss is employed for locating the
potency of the electrical device.
The short check is performed on the high
voltage winding of the electrical device.
the total load current is measured by the meter
connected across their high voltage winding
.
Figure
Full Load Test or Short Circuit Test
Table
Full Load Test Data for Distribution Transformer
Transformer kVA
rating |
Full-
load loss (W) |
Impedance
Voltage (V) |
10 |
90.7 |
163 |
10 |
92.1 |
168 |
10 |
90.3 |
165 |
10 |
91.4 |
166 |
No-Load Loss Test
No load check
is additionally referred to as circuit check. No load loss check is employed to
see core loss in electrical device. No load losses consisting of the physical
phenomenon loss and also the eddy current loss. The voltage at fifty cycle per
second frequency is applied thereto fifty-five aspect with the assistance of three-part
voltage offer regulator. The HV aspect of the electrical device is unbroken
open. For this check we'd like a watt meter, 3-part voltage offer and clamp
meter. For checking the no load test initially, we have a tendency to connect 3-part
offer to LT terminals. At this check LT neutral terminal & HT terminals ar
unbroken open. once the applied voltage is traditional voltage then traditional
flux are found out. because the Iron loss may be a perform of applied voltage,
traditional iron loss can occur. therefore, the iron loss is most at rated
voltage. Then we have a tendency to applied 403 V (red), 402 V (yellow), 395 V
(blue) rated voltage in LT terminal with the assistance of 3 part voltage for
measurement the no load current, we have a tendency to hold the clamp meter
within the three-phase wire in LT aspect. The holding method of clamp meter has
shown in figure six.1.9. For ten kVA we have a tendency to live the no load
current in LT terminal is six.69 A, 6.51 A and 4.88 A. A wattmeter is connected
with LT aspect. This most iron loss is measured victimization the wattmeter.
This check solely measures the combined iron losses consisting of the
hysteric’s loss and also the eddy current loss. though the hysterics loss is a
smaller amount than the eddy current loss, it's not negligible. Since the HT
terminals of the electrical device ar open, the LT terminals attracts solely
no-load current, which is able to have some copper loss. This no-load current
is extremely little and since the copper loss within the LT is proportional to
the sq. of this current, it's negligible. there's no copper loss within the HT
as a result of there's no HT current. For one hundred kVA electrical device no
load loss shown ten.5 W in watt meter. The watt meter issue is a pair of. So,
we've got to multiply the wattmeter reading with a pair of. For one hundred kVA
electrical device no load loss is a pair of *10.5 = twenty-one watt. Then no
load check result's recorded in check result kind. The recorded in check result
kind for one hundred kVA electrical device check listed below:
Table : No Load Loss Test
SL |
Transformer
serial no |
kVA
rating |
No
load loss test (watt) |
1 |
2017-10-48770 |
100 |
21.70 |
2 |
2017-10-48550 |
100 |
22.20 |
3 |
2017-10-48796 |
100 |
22.50 |
4 |
2017-10-49163 |
100 |
22.60 |

Figure : No Load Loss Test
High
volt side (V) |
Line
current (A) |
Three
phase power (watt) |
403 |
6.69 A |
|
402 |
6.51 A |
300*2*2 |
395 |
4.88 A |
|
The purpose of the no
load takes a look at is to work out the no load current and losses of the
electrical device, that is verify their no-load parameter. within the no load
take a look at or circuit take a look at we have a tendency to open the first
sides of the electrical device. then we have a tendency to area unit offer 240
V within the secondary aspect. A meter, meter and a wattmeter area unit
connected with the within the secondary aspect. The reading of the wattmeter
solely represents the core and iron losses.
|
Figure
No Load Test
Table : No Load Test Data for Distribution Transformer
Transformer kVA
rating |
No load
current (A) |
No load
loss (W) |
10 |
0.13 |
12.3 |
10 |
0.17 |
11.3 |
10 |
0.14 |
12.2 |
10 |
0.16 |
11.9 |
Winding Resistance Test
For measure winding resistance take a look at solely, a
multimeter is wanting. In winding resistance take a look at LT facet
affiliation ought to be open. no voltage supply is needed. Winding resistance
solely measured in HT facet. initially 2 terminals of multi connected to the HT
A and B terminal. Then activate the multimeter and set it pointer in ohm for
measure resistance. stay up for few second. Result can show in millimeters
show. once measure resistance in HT, A, I live HT B and C terminal winding
resistance. Then output results shown in multimeter. Then we tend to live HT A and C terminal. And
last once measure the winding resistance HT A and B, B and C, C and A terminal
in a hundred kVA electrical device.
Table : Winding resistance
measurement
Terminal-1 |
Terminal-2 |
Resistance
(Ω) |
A |
B |
12.4
Ω |
B |
C |
12.4
Ω |
C |
A |
12.4
Ω |
Ratio Test
The performance of a electrical
device for the most part depends upon perfection of specific turns or voltage
quantitative relation of electrical device. So, electrical device quantitative
relation takes a look at is an important take a look at of electrical device.
The voltage ought to be applied solely within the high voltage winding so as to
avoid unsafe voltage. {to take a look at|to check} electrical device
quantitative relation test we want three-part offer, multimeter and Clamp
meter. three-part offer is provided in HT terminal. By multimeter we tend to
live output voltage. And Clamp meter for measure current. First, the faucet
changer of electrical device is unbroken within the position 3 (3) and cardinal
terminals ar unbroken open. Then apply three-part offer on HV terminals that
shown in figr1. live the voltages applied on every part (Phase-Phase) on HV and
induced voltages at cardinal terminals at the same time. three-part voltage offers
regulators. From that regulator we tend to offer three-part voltage to the HV
terminal. I will increase or decrease voltage by regulator switch. Red, Yellow,
blue color indicates three-part voltage. By regulator switch I increase
voltage. In HT terminals three-part voltage ar 402 V (red), 404 V (yellow), and
411 V (blue).
The procedure of transformer ratio
test is simple. We just apply 240 AC supply to the primary winding and took the
value from secondary winding with the help of voltmeter. But the ratio test
machine is converting the voltage into turn ratio and show the ratio value the
formula of turn ratio is
K=VP/VS
For a single-phase distribution
transformer, the ideal ratio is 26.30 to 26.50. This ratio is considered as
ideal for a single-phase distribution transformer where Primary voltage is 6350
V and secondary voltage is 240 V.
Table Ratio test Data for
Distribution Transformer
Transformer kVA rating |
Voltage Ratio |
10
|
26.473 |
10
|
26.469 |
10
|
26.482 |
10
|
26.457 |
10
|
26.489 |
Transformer Oil Test
For transformer oil test I have a machine which called ASTM
D877. The full from of ASTM is American Standard Testing Machine. The whole
test took only 5 min itself. It gives five results and end of all it also gives
an average result. In 220 V and 50 HZ the machine starts, it is the rated value
for that machine. Inside the machine there is there is two cathode rods. The
gap is this two-cathode rod is 2.5. If the gap is more or less than the rated
gap, the result will not may come appropriately. They picked a sample of oil and put inside
the cathode rod. Start the machine for 5 mines. And in this five min it gives
us five results. The result of oil test is 18.5,24.5. This oil was from an old
transformer so expect result was above 20. As the result is 24.5, I can say
that the oil is fine. If I test new transformer oil the result needs to come
above 30
Table : Oil Test Measurement
Result |
|
1st |
21.4
kV |
2nd |
23.5
kV |
3rd |
24.7
kV |
4th |
27.4
kV |
5th |
27.8
kV |
Continuity Test of transformer
The purpose of this test is to
Checking the continuity both primary windings and secondary windings of a
transformer by megger. For this test, a megger is connected across with primary
and secondary windings of the transformer. If the megger gives very low Mega
Ohm resistance this, mean that the winding wire is perfect (or have
continuity). Otherwise, it is not perfect (or has discontinuity).
Table
Continuity Test Data for Distribution Transformer
Transformer
kVA rating |
Winding
Resistance (HT-HT)
M Ohm |
Winding
Resistance (LT-LT)
M Ohm |
10 |
0 |
0 |
10 |
0 |
0 |
From the above data table, we can
say that, here is no breakdown in the transformer coil.
Insulation Resistance Test of transformer
It is commonly known as the Megger test.
This test is ensuring the quality of all insulation system within a transformer.
This is the resistance measurement of the windings by applying megger between
primary winding and secondary winding.
Figure
Insulation Resistance Test
The tank and core of a transformer
should always be grounded when this test is performed. Resistances are then
measured between each winding and all other windings and ground. If the megger
gives the resistance 1000 plus Ohm then insulation resistance is perfect
otherwise, they have to change the insulation.
Table
Insulation Resistance Test Data for Distribution Transformer
Transformer
kVA Rating |
Insulation
Resistance test |
Measured Value M Ohm |
10 |
HT-LT |
6000 |
10 |
HT-Body |
6000 |
From the above data table, we can say
that, the insulation of the transformer coil is satisfactory.
Polarity Test of transformer
This test is needed for identifying a
transformer either additive or subtractive. When voltage is applied between the
primary bushings and the resultant voltage between the secondary bushings is
greater, and then it means that the transformer has additive polarity. When
voltage is applied between the primary bushings and the resultant voltage
between the secondary bushings is lesser and then it means that the transformer
has subtractive polarity.
Table
Polarity Test Data for Distribution Transformer
Transformer kVA
rating |
Supply
voltage |
Induced Voltage |
Measuring voltage |
Polarity |
10 |
236 V |
8.9 V |
245 V |
Additive |
10 |
237
V |
8.9
V |
243 V |
Additive |
10 |
235 V |
8.9
V |
227 V |
Subtractive |
10 |
235
V |
8.9
V |
243
V |
Additive |
In PBS system for distribution transformer they make the transformers which have additive polarity and for power transformer they make it as subtractive polarity.
How can you tell if a transformer is bad?
If transformer test result show error or failed. That’s way
we say that transformer is bad.
Why transformer testing is required?
Transformer testing is required because we make sure that transformer condition is good or bad that’s way transformer testing is required.
Can a transformer get weak?
In
the transformer get weak because when oil and some material are not work and
transformer test result show error, in those purpose transformers get weak.
0 Comments